Material
Polyamide (PA 6.6), 25% fiberglass-reinforced.
Continuous operating temperature max. 130°C.
Fire protection coresponding to UL 94-V0.
Additional Information
Construction width: 105 mm
Height: 240 mm
Rated current up to: 250 amps
Rated operating voltage: 690 volts AC
Connection of cables/wires: 1-4/0 AWG ( 35-120 mm2)
Clamping area for laminated copper bars: 18.5x15.5 mm
Tightening Torque:
-Busbar attachment, 4-6 Nm
-Terminal screw, 8-10 Nm
For use with cicuit breaker models:
-ABB, S3 / T3 / T4
-Eaton JG
-GE, FE
-Merlin Gerin, NS100 / NS160 / NS250
-Moeller Electric, NZM2
-Siemens, VL160X / VL160 / VL250
-Telemecanique, GV7
For busbar thickness: 5 or 10 mm
One CB component adaptor is included per pack.
|