Material
Polyamide (PA 6.6), 25% fiberglass-reinforced.
Continuous operating temperature max. 130°C.
Fire protection coresponding to UL 94-V0.
Additional Information
Construction width: 140 mm
Height: 324 mm
Rated current up to: 630 amps
Rated operating voltage: 690 volts AC
Connection of cables/wires: max 250 MCM (max 150 mm2) with ring terminal
Clamping area for laminated copper bars: 32x10 mm
Tightening Torque:
-Busbar attachment, 12-14 Nm
-Terminal screw, 30-32 Nm
For use with cicuit breaker models:
-ABB, S5 / T5
-Eaton LG 400/630A
-Merlin Gerin, NS400 / NS630
-Moeller Electric, NZM3
-Siemens, VL400 / VL630 (with 9342720, 25 mm width insert)
For busbar thickness: 5 or 10 mm
One CB component adaptor is included per pack.
|